13. Earthing and Grounding Calculations

Principle

Earthing (grounding) provides a reference point of zero volts for the electrical system and a safe path for fault currents. This ensures that overcurrent devices operate correctly and reduces touch voltages for safety. Earthing design calculations focus on:

  • Earth fault loop impedance: To ensure sufficient current flows during a line-to-earth fault so that protective devices trip within the required time (per BS 7671, NEC, etc.).
  • Ground electrode resistance: The resistance of earth rods or grids that dissipate fault or lightning currents into the soil.
  • Step and touch voltages: In large earth grids (such as substations), these calculations ensure the voltages are below tolerable limits based on fault current and grid geometry.
  • Conductor sizing for fault current: Using the adiabatic heating formula to size earth conductors so they do not melt during a fault.

Earth Fault Loop Impedance and Disconnection Time

For a given circuit, the loop impedance (Zs)—which includes the source (e.g., transformer winding), line conductor, and the return path (CPC and possibly the earth/ground path in a TT system)—is calculated by summing the resistances of each component. Once Zs is known, the prospective earth fault current is:

If = U₀ / Zs

(Here, U₀ is the phase-to-neutral voltage for a single-phase fault.) The protective device must interrupt this fault current within a specified time (e.g., 0.4 s for final circuits in TN systems per BS 7671). BS 7671 provides maximum Zs values for each protective device, essentially as:

Zs ≤ U₀ / I₂

where I₂ is the current needed to ensure trip within time. Designers calculate Zs from cable lengths, sizes, and transformer source impedance, ensuring it is below the maximum. If not, either larger conductors or additional bonding is required.

TT Systems and Touch Voltage

For TT (Terra-Terra) systems, the sum of the electrode resistance and the earth conductor resistance (RA) is used along with the RCD trip current (IΔn) to ensure:

RA × IΔn ≤ 50 V

This calculation ensures that touch voltages remain safe.

Ground Electrode Resistance

A basic formula for a single rod electrode (of length L and diameter d) in homogeneous soil (with resistivity ρ) is derived from integrating the spreading resistance along the rod. For example, consider a 12 mm diameter rod, 3 m long, in soil with ρ = 100 Ω·m:

R ≈ [100 / (2π×3)] × (ln(43/0.012) − 1)

In practice, if the calculated resistance is high (e.g., ~31 Ω in this example), multiple rods or a grid is used to achieve a target resistance below, say, 10 Ω.

Step and Touch Voltage Calculations

In substations, an earth grid is installed under a gravel bed. Under fault conditions, not all parts of the grid remain at 0 V; portions may rise in potential relative to remote earth.

  • Touch voltage: The voltage difference between a person’s hands (attached to the grid) and feet (on the earth).
  • Step voltage: The voltage difference between two points on the earth (typically 1 m apart).

IEEE 80 and equivalent IEC standards provide formulas to estimate these voltages based on grid geometry, fault current, and soil resistivity. Designers compute the grid resistance (Rg) and current splits, comparing the results to safe limits. If the computed step/touch voltage exceeds acceptable levels, adjustments (such as adding more electrodes or increasing mesh density) are made.

Conductor Sizing (Earthing Conductors)

Earth and bonding conductors must safely carry fault current for the brief time until disconnection occurs without melting. The adiabatic formula used is:

I²t = (kS)²

where S is the cross-sectional area (in mm²), If is the fault current (in A), t is the duration (in s), and k is a material constant (for copper, typically ≈115 when considering a temperature rise from 90°C to 250°C). For example, if a 10 kA fault lasts 0.1 s:

I²t = (10,000)² × 0.1 = 10⁸ A²s

Then, for copper with k = 115:

S = √(10⁸) / 115 ≈ 27.7 mm²

A 35 mm² earth conductor would thus be adequate. In practice, standards provide tables correlating I²t values with conductor sizes.

Niche Considerations

  • Soil resistivity surveys: These are performed on large projects to obtain accurate ρ values. If layered soil is found, a two-layer soil model may be used.
  • Ground rings for buildings: Many codes require a ground ring electrode (e.g., NEC recommends a minimum of 20 ft of #2 AWG bare conductor). Often, simple design rules suffice.
  • Lightning protection grounding: Calculations for lightning differ, focusing on high-frequency impedance and equipotential bonding. Standards such as NFPA 780 or BS EN 62305 address these requirements.
  • Substation earthing system testing: Current injection tests or fall-of-potential tests are used to measure actual ground resistance and step/touch voltages.
  • Corrosion and ground grids: In corrosive soils, choices such as copper rods or the application of cathodic protection become critical.
  • Ground fault current split: In systems with combined neutral-earth (such as TN-C), the return path of fault current must be analyzed to determine whether the metallic or soil path dominates.

Industry Relevance

Proper earthing is fundamental for electrical safety. Calculations ensure that if a phase conductor contacts a machine frame, the resulting fault current is sufficient to trip protective devices quickly—reducing the risk of electric shock. In supply networks, effective earthing helps control touch voltages during faults. Additionally, earthing affects electromagnetic compatibility by providing a reference for shielding. Poor earthing can lead to erratic RCD trips or dangerously high step voltages.

Standards

  • BS 7430: The UK Code of Practice for Earthing, covering design methods from domestic TT systems to substations.
  • IEEE Std 80: An authoritative guide for AC substation grounding, including formulas for grid resistance and touch voltage.
  • NFPA 70 (NEC), Article 250: Provides grounding and bonding rules in the US, referencing IEEE 80 for detailed design.
  • IEC 60364-5-54: Addresses earthing arrangements and protective conductors in low-voltage installations.
  • EN 62305 and UL Standards: Cover lightning protection grounding and ensure low-resistance connections over time.

Software Tools

  • Ground grid design software: SES CDEGS is a comprehensive suite for modeling arbitrary electrode configurations and soil layering to compute resistance and step/touch voltages.
  • ETAP Grounding Module: Allows modeling of ground grids and computes safety voltages using methods similar to IEEE 80.
  • Simple Calculators and Spreadsheets: Many electrode manufacturers offer online calculators or spreadsheets for estimating single rod or array resistances.
  • Soil Resistivity Measurement Software: Tools to process Wenner 4-pin test data and derive layered soil models.
  • Short-Circuit Programs: Some integrated tools compute earth fault currents and their distribution through different return paths.
  • Touch Voltage Spreadsheets: Internal models based on IEEE 80 equations to perform quick checks.

Conclusion

Earthing calculations combine theoretical formulas with empirical design rules. By following established standards and using specialized tools, engineers design grounding systems that protect people from electric shock and ensure that equipment withstands fault conditions.